PHASE |
3-phase in / 1-phase out |
CAPACITY |
20000 VA/16000 W |
20000 VA/16000 W |
INPUT |
Nominal Voltage |
3 x 400 VAC (3Ph+N) |
Voltage Range |
305-478 VAC (3-phase) at 100% load ; 190-520 VAC (3-phase) at 50% load |
Frequency Range |
46~54Hz or 56~64Hz |
Power Factor |
≧ 0.99 @ 100% Load |
THDi |
< 6% @ 100% load |
OUTPUT |
Output Voltage |
208/220/230/240VAC |
104/110/115/120VAC or 208/220/230/240VAC |
AC Voltage Regulation (Batt. Mode) |
± 1% |
Frequency Range (Synchronized Range) |
46~54Hz or 56~64Hz |
Frequency Range (Batt. Mode) |
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Current Crest Ratio |
3:1 |
Harmonic Distortion |
≦ 2 % THD (Linear Load) ≦ 5 % THD (Non-linear Load) |
≦2 % THD (Linear Load) ≦7% THD (Non-linear Load) |
Transfer Time |
AC Mode to Batt. Mode |
Zero |
Inverter to Bypass |
Zero |
Waveform (Batt. Mode) |
Pure Sinewave |
EFFICIENCY |
AC Mode |
89% |
87% |
Battery Mode |
87% |
83% |
BATTERY |
Standard Model |
Battery Type |
12 V / 9 Ah |
Numbers |
20 pcs (18 - 20 pcs adjustable)* x 2 strings |
N/A |
Typical Recharge Time |
9 hours recover to 90% capacity |
Charging Current (Max.) |
2A |
Charging Voltage |
273 VDC ± 1% (Based on 20pcs batteries) |
Long-run Model |
Battery Type |
Numbers |
Charging Current (Max.) |
8A |
8A |
|
Charging Voltage |
273 VDC ± 1% (Based on 20pcs batteries) |
INDICATORS |
LCD Display |
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
ALARM |
Battery Mode |
Sounding every 4 seconds |
Low Battery |
Sounding every second |
Overload |
Sounding twice every second |
Fault |
Continously sounding |
PHYSICAL |
Standard Model |
Dimension, DxWxH (mm) |
815 x 250 x 826 |
N/A |
|
Net Weight (kgs) |
164 |
|
Long-run Model |
Dimension, DxWxH (mm) |
592 x 250 x 576 |
815 x 250 x 826 |
|
Net Weight (kgs) |
40 |
141 |
|
ENVIRONMENT |
Humidity |
0-95 % RH @ 0- 40°C (Non-condensing) |
Noise Level |
Less than 60dB @ 1 Meter |
MANAGEMENT |
Smart RS-232/USB |
Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8, Linux, Unix, and MAC |
Optional SNMP |
Power management from SNMP manager and web browser |