تعمل هذه السلسلة على طوبولجية حقيقية عبر مسار الدائرة الكهرباية.يضمن الجهد المزدوج جهد خرج سلامة و استقرارية التطبيقات الحساسة و الدقيقة , فهو يؤمن فقدان بياناتك من انقطاع التيار الكهربائي, ارتفاعه او ضعفه. يسمح لك نطاق جهد الدخل الواسع بتقييد إستخدام البطارية, مما يؤدي الى زيادة عمر البطارية
| Model | ORVALDI VT1K online | ORVALDI VT2K on-line | ORVALDI VT3K online |
| Part no | VWPP1K | VWPP2K | VWPP3K |
| Capacity | 1000V A / 900W | 2000V A / 1800W | 3000V A / 2700W |
| INPUT | |||
| Voltage Range | 120-300VAC @ 50% of load, 180-280VAC @ 100% of load | ||
| Frequency range | 40 ~ 70 Hz | ||
| Power factor | ≥0.99 @ 100% of load | ||
| OUTPUT | |||
| Output Voltage | 200/208/220/230 / 240VAC (programmable) | ||
| AC Voltage Regulation (Batt. Mode) | ± 1% | ||
| Frequency Range (Synchronized Range) | 47 ~ 53Hz or 57 ~ 63Hz | ||
| Frequency Range (Batt. Mode) | 50Hz or 60Hz ± 0.5% | ||
| Waveform (Batt. Mode) | Pure sinewave | ||
| Current Crest Ratio | 3: 1 | ||
| Harmonic Distortion | ≤ 3% THD (Linear Load), ≤ 6% (Non-Linear load) | ||
| Transfer time (AC Mode to Batt. Mode) | 0ms | ||
| Transfer Time (Inverter to Bypass) | 4ms | ||
| EFFICIENCY | |||
| AC Mode | 88% | 89% | 90% |
| Battery Mode | 83% | 85% | 88% |
| BATTERY | |||
| Numbers | 2 x 9Ah | 4 x 9Ah | 6 x 9 Ah |
| Recharging time | 4 hours to 90% capacity | ||
| Charging Current (Max.) | 1A max | ||
| Charging Voltage | 27.4VDC ± 1% | 54.7VDC ± 1% | 82.1VDC ± 1% |
| INDICATORS | UPS status, Load level, Battery level, Input / Output voltage, Discharge timer and Fault conditions | ||
| ALARM | |||
| Battery Mode | Sounding every 4 seconds | ||
| Low Battery | Sounding every second | ||
| Overload | Sounding twice every second | ||
| Fault | Continuously sounding | ||
| PHYSICAL | |||
| Dimension, LxWxH (mm) | 282 x 145 x 220 | 397 x 145 x 220 | 421 x 190 x 318 |
| Net Weight (kgs) | 9.8 | 17 | 27.6 |
| ENVIRONMENT | 20-90% at 0- 40 ° C (Non-condensing) | ||
| Noise Level | Less than 50dB @ 1 Meter | ||
| MANAGEMENT | |||
| RS-232 / USB | Supports Windows® 2000/2003 / XP / Vista / 2008, Windows® 7/8, Linux, Unix, and MAC | ||
| Optional SNMP / AS 400 | Power management from SNMP manager and web browser | ||